Huawei h12-425 practice test

HCIP-Data Center Facility Deployment V2.0

Last exam update: Dec 11 ,2025
Page 1 out of 4. Viewing questions 1-15 out of 55

Question 1

Which air supply mode requires reasonable raised floor height?

  • A. Air supply mode using blast caps.
  • B. Underfloor air supply mode
  • C. Air supply mode using wind pipe
  • D. In-row horizontal air supply mode
Mark Question:
Answer:

B

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 2

Which of the following statements is true about UPS5000 power modules and bypass modules?

  • A. The UPSS000-E-200K and UPS5000-E-400K use the same power module and provide the same capacity of 50 kVA but have different numbers of power modules.
  • B. For UPSs of the same model but in different power segments, their bypass module capacity is the same.
  • C. The power module capacity of both the UPS5000-S and UPS5000-E is 50 kVA. Therefore, the two types of UPS can be used together.
  • D. The power modules used in the UPSS000-S-1200K are the same as those used in the UPS5000-E- 200K.
Mark Question:
Answer:

A

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 3

In operant conditioning, the subject is free to make responses at any time, So conditioning is
measured by the rate of responding. In most other Ways, however, their forms of learning are
essentially the same.

  • A. When UPSs are connected in parallel, connect loads to the pL terminal.
  • B. When a single UPS works and loads are of the same importance, connect all loads to the sL terminal.
  • C. When a single UPS works and loads are divided into two levels, connect the primary load to the sL terminal and the secondary load to the pl_ terminal.
  • D. When the UPS is overloaded, the loads connected to the sL terminal will be powered off first to ensure continuous power supply to the loads connected to the pj_ terminal.
Mark Question:
Answer:

D

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 4

What is the input/output voltage range of the SmartLi BCU?

  • A. 280415 V
  • B. 300400 V
  • C. 300480 V
  • D. W00-544 V
Mark Question:
Answer:

C

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 5

To determine whether the R410A refrigerant meets requirements, compare the internal pressure of
the refrigerant with the saturation pressure corresponding to the refrigerant temperature. If the
difference between the internal pressure and the saturation pressure is within the range of which of
the following, replace the refrigerant?

  • A. 0-0.05 MPa
  • B. 0.05-0.1 MPa
  • C. 0.1-0.2 MPa
  • D. 0.25-0.3 MPa
Mark Question:
Answer:

B

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 6

Which of the following statements is false about the ECM of the UPS5000-E?

  • A. As a control interface for the entire system, the ECM communicates with each module and provides a bus for communication between the dry contact card and the system control card.
  • B. The ECM controls the bypass module to work properly, if one ECM is faulty, the UPS can still work in normal mode but cannot be manually switched to bypass mode.
  • C. The ECM ensures equalized output currents between modules so that load power is equally shared.
  • D. The ECM provides three types of CAN communication: monitoring CAN communication, intra-rack parallel CAN communication, and inter-rack parallel CAN communication.
Mark Question:
Answer:

B

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 7

Due to simple operations and easy interconnection, which of the following communication types is
recommended for NetEco northbound integration?

  • A. WebService
  • B. SNMP
  • C. FTP
  • D. PoE
Mark Question:
Answer:

A

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 8

Which of the following PH values meets the water quality requirements of NetCol8000-E220?

  • A. 3
  • B. 5
  • C. 7
  • D. 9
Mark Question:
Answer:

C

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 9

In the FusionModule2000, if a device port complies with the Modbus RTU protocol, which device is
used to connect to smart ETH gateway?

  • A. ETH converter
  • B. Access actuator
  • C. Skylight actuator
  • D. AC actuator
Mark Question:
Answer:

A

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 10

In a project 32 NetCol8000-Cs need to be networked for teamwork. Each group consists of four air
conditioners. How should the northbound RS485 grouping switches, namely, toggle switches 2 and 3
on the main control module, be set for the last air conditioner in each group?

  • A. ON, ON
  • B. ON, OFF
  • C. OFF, ON
  • D. OFF, OFF
Mark Question:
Answer:

D

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 11

Which of the following statements about the functions of the AC PDB is false?

  • A. Supplies power to air conditioners.
  • B. Supplies power to fans.
  • C. Supplies power to the extinguishant control panel.
  • D. Supplies power to sockets in the modules.
Mark Question:
Answer:

D

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 12

Which of the following position is recommended for installing the smart ETH gateway?

  • A. Control skylight
  • B. Inside a network cabinet
  • C. At the inner side of a door header
  • D. At the side of a cable trough
Mark Question:
Answer:

B

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 13

When installing a water-cooled module, what is the minimum distance between the module and the
wall?

  • A. 300 mm
  • B. 400 mm
  • C. 500 mm
  • D. 600 mm
Mark Question:
Answer:

D

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 14

On the ECC800-Pro WebUI, which of the following is the first-level menu of the NMS Application?

  • A. System Settings
  • B. Maintenance
  • C. Home
  • D. Monitoring
Mark Question:
Answer:

A

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000

Question 15

The UPS5000-E-200K works in normal mode. If two ECMs are faulty, how does the UPS work?

  • A. The UPS has no output.
  • B. The UPS transfers to bypass mode.
  • C. The LCD is off, but the UPS still works in normal mode.
  • D. The UPS switches to battery mode.
Mark Question:
Answer:

B

User Votes:
A
50%
B
50%
C
50%
D
50%
Discussions
vote your answer:
A
B
C
D
0 / 1000
To page 2